12 active routines · 42 preventive tasks due today · 7 overdue.
Due today
42
Daily + weekly cycle
Overdue
7
Action required
+2 vs week
Coverage 30d
94%
Completed vs scheduled
Failed audits 90d
0
All passes / pass-with-notes
Due today / overdue
| Routine | System | Cadence | Owner | Last done | Next due |
|---|
Upcoming this month
| Routine | Cadence | Procedure | Regulatory basis | Next |
|---|---|---|---|---|
| Pool chemistry · pH/ORP/free Cl | daily | Sample 3 stations, log to BMS, dose if out of band. | ME Sanitary code §14.2 | 2026-04-18 |
| Fire detection walk-through | weekly | Activate 1 detector per zone, verify panel + remote alarm. | EN 54 | 2026-04-19 |
| Cold-water tank inspection | weekly | Free chlorine + visual sediment check. | — | 2026-04-19 |
| Generator weekly test run | weekly | 30-min loaded run · log frequency, voltage, fuel. | — | 2026-04-20 |
| BMS device health audit | weekly | Coverage report, missing devices triage. | — | 2026-04-22 |
| Kitchen hood grease audit | quarterly | Visual + ATP swab; schedule deep clean if grade <B. | NFPA 96 | 2026-04-22 |
| Elevator C · annual statutory | annual | Vendor visit (Schindler) · brake test, governor, ropes. | EN 81-20 | 2026-04-22 |
| Hyperbaric chamber safety audit | monthly | Seal integrity, pressure decay, O₂ analyser. | ASME PVHO-1 | 2026-04-30 |
Recent completions
| When | Routine | By | Outcome | Findings |
|---|---|---|---|---|
| 2026-04-17 07:00 | Pool chemistry · pH/ORP/free Cl | Goran Petrovic | pass | pH 7.6 (band) · free Cl 1.2 mg/L · ORP 720 mV. |
| 2026-04-15 14:20 | BMS device health audit | Veljko Spasojevic | pass with notes | 1 leak sensor on D-7 stack offline — replaced (rtn.D704 incident). |
| 2026-04-13 06:00 | Generator weekly test run | Bojan Zivkovic | pass | Loaded run 30 min · 49.97 Hz · fuel @ 92%. |
| 2026-04-12 10:00 | Fire detection walk-through | Nemanja Lukic | pass | All zones cleared in 47 min. |
| 2026-04-12 09:15 | Cold-water tank inspection | Goran Petrovic | pass | Free Cl 0.42 mg/L · no sediment. |
| 2026-04-10 13:00 | Spa fan-coil drain pan check | Dragan Ilic | pass with notes | FC-02 setpoint deviation flagged · raised WO. |
| 2026-04-04 08:30 | VRF filter rotation · floors 2–4 | Dragan Ilic | pass with notes | AHU-3 (B-floor 4) filter EOL · replaced. |
| 2026-03-30 11:00 | Hyperbaric chamber safety audit | Nemanja Lukic | pass | Pressure decay <0.5% / 30 min · O₂ analyser calibrated. |
| 2026-02-14 09:00 | Dry riser hydrostatic test | Nemanja Lukic | pass | 12 bar held for 60 min · no drop. |
| 2026-01-08 15:00 | MV switchgear thermography | Bojan Zivkovic | pass | All panels within 10°C delta. No anomalies. |